Air-to-Water Heat Pump
Chillers
Continental’s Air-to-Water
Heat Pump Chillers feature advanced rotary screw compressor
technology, brazed plate evaporator/condenser and copper tube
and aluminum fin condenser/evaporator. Each refrigerant circuit
is complete with a filter drier, sight glass, solenoid valve,
expansion valve and reversing valve. The NEMA 12 control center
is complete with all power, operating and safety controls, and
is ETL listed to UL 508A. All components are mounted on one
common skid, constructed from structural steel welded to form a
solid heavy-duty frame.
Models HPAR offer high efficiency in both cooling and heating
modes, due to the fact that the heat transfer surfaces are
generously sized.
Part load performance is automatically controlled between 100%
to 25%, and all values in between – to match the load.
Models HPAR use outside ambient to provide hot water. In most
cases, the limiting factor is the outside ambient. The practical
design ambient temperature is 35° F. Below 35° F, one option is
to have factory supplied supplemental heat or a backup HPAR
system that will defrost while the main system is heating.
Continental’s open protocol BACnet controller further enhances
the product application and can be used with many building
control systems.
Continental’s chillers are
Engineered Green™
by using
environmentally-friendly, non-ozone depleting refrigerant
technology for energy-efficiency.
Let our engineers help you get more for your money – on your
installation and operation – by customizing an Air-to-Water Heat
Pump Chiller to optimize your application. Continental is proud
to offer over 35 factory supplied options with its chillers. Get
the most out of a Continental Air-to-Water Heat Pump Chiller
system by adding:
For assistance
with selection and system optimization, contact Continental’s
Application Engineering Department at 888-CHILL11 (888-244-5511)
or
sales@continentalteam.com. Or fill out our online inquiry
form – it’s fast and easy. No “required” fields, no “automated”
responses – we guarantee a person, not a computer, will promptly
answer your inquiry.
|
Model |
Number
of Circuits |
Cooling
Tons 1 |
Heating
Mbh
2 |
Supplemental kW Available 3 |
Water
GPM |
Water
Connections, “ |
Unit
MCA @ 460V * |
Dimensions |
|
L” |
W ” |
H” |
|
HPAR-50 |
1 |
37 |
477 |
15, 20 |
89 |
2.5 |
84 |
108 |
86 |
54 |
|
HPAR-60 |
1 |
47 |
615 |
15, 20 |
113 |
2.5 |
114 |
108 |
86 |
54 |
|
HPAR-70 |
1 |
54 |
673 |
20, 30 |
130 |
2.5 |
136 |
144 |
86 |
54 |
|
HPAR-80 |
1 |
63 |
806 |
20, 30 |
151 |
4 |
142 |
144 |
86 |
54 |
|
HPAR-90 |
1 |
73 |
944 |
20, 30 |
175 |
4 |
162 |
144 |
86 |
54 |
|
HPAR-102 |
2 |
74 |
954 |
20, 30 |
178 |
4 |
147 |
144 |
86 |
54 |
|
HPAR-110 |
1 |
89 |
1095 |
20, 30 |
214 |
4 |
239 |
144 |
86 |
54 |
|
HPAR-122 |
2 |
94 |
1230 |
30, 40 |
226 |
4 |
201 |
192 |
86 |
56 |
|
HPAR-120 |
1 |
103 |
1296 |
30, 40 |
247 |
4 |
264 |
192 |
86 |
54 |
|
HPAR-142 |
2 |
107 |
1346 |
30, 40 |
257 |
4 |
237 |
192 |
86 |
56 |
|
HPAR-140 |
1 |
120 |
1526 |
20, 30 |
288 |
4 |
302 |
192 |
86 |
56 |
|
HPAR-162 |
2 |
126 |
1612 |
30, 40 |
302 |
5 |
247 |
232 |
86 |
56 |
|
HPAR-182 |
2 |
146 |
1888 |
40, 50 |
350 |
6 |
284 |
232 |
86 |
56 |
|
HPAR-180 |
1 |
152 |
1868 |
40, 50 |
365 |
6 |
423 |
232 |
86 |
56 |
|
HPAR-222 |
2 |
178 |
2231 |
40, 50 |
428 |
6 |
352 |
272 |
86 |
56 |
|
HPAR-210 |
1 |
178 |
2231 |
40, 50 |
428 |
6 |
510 |
272 |
86 |
56 |
1
cooling tons are based on ARI conditions of 54/44° F chilled
water/95° F ambient
2 heating Mbh is based on 35° F ambient and 120° F
hot water temperature
3 supplemental kW of electric heat available as an
option
* For 208/230 V or 575 V, contact factory |